18
11.3 THREE-WIRE START/STOP CONTROL
NOTES:
1. Program TB-13E (Parameter 12) for START FORWARD (06).
2. If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) for START REVERSE (07).
3. Momentarily close TB-13E to TB-11 to START in the forward direction, or close TB-13A to
TB-11 to START in the reverse direction. Momentarily open TB-1 to TB-11 to STOP the
drive.
4. For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE (Parameter
05) to 0-10 VDC (03) or 4-20 mA (04).