SPEEDMASTER®Micro Series CompactInverters Installation and Operation ManualA Regal Brand

Página 2

84.2 TYPE 1 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac and 60 HP at 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N C P Q S

Página 3 - TABLE OF CONTENTS

94.3 WASHGUARD NEMA 4/12, 12, & 4X* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. Slo

Página 4 - TABLE OF CONTENTS (cont’d.)

10WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q

Página 5 - IMPORTANT NOTICE

114.4 TYPE 12 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac AND 60 HP AT 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N P Q

Página 6 - 1.0 GENERAL

12* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF

Página 7

135.0 MICRO SERIES RATINGS115/230 & 230V (SINGLE PHASE) VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (120/240 Vac, 50-60 Hz) (0-230 Vac)

Página 8 - 4.0 MICRO SERIES DIMENSIONS

14230 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (200/240 Vac, 50-60 Hz) (0-200/230 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Página 9

15460 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (400/480 Vac, 50-60 Hz) (0-400/460 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Página 10 - Small holes = 1.13”

16575 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (480/590 Vac, 50-60 Hz) (0-460/575 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Página 11 - Others are NEMA 4/12

6.0 THEORY6.1 DESCRIPTION OF AC MOTOR OPERATION ThreephaseACmotorsarecomprisedoftwomajorcomponents,thestatorandtherotor.Thestatoris

Página 13

 Ifthefrequencyappliedtothemotorisincreasedwhilethevoltageremainsconstant,torquecapabilitywilldecreaseasspeedincreases.Thiswill

Página 14

 “Variabletorque”referstothefactthatthetorquerequiredvarieswiththesquareofthespeed.Also,the horsepower required varies with th

Página 15 - 5.0 MICRO SERIES RATINGS

6.2.3 MICRO SERIES INPUTS AND OUTPUTS Thedrivehas two analog inputs (0-10 VDC and 4-20 mA) that can beused for speed reference, PI

Página 16 - OTHERS ARE NEMA 1 ENCLOSURE

The following describes the possible relay output settings: NONE This setting disables the relay output. RUN The relay energizes when the dri

Página 17

7.0 INSTALLATION DRIVESMUSTNOTBEINSTALLEDWHERESUBJECTEDTO ADVERSE ENVI- RONMENTAL CONDITIONS! DRIVES MUST NOT BE INSTALLED WHERESUBJ

Página 18

7.1 INSTALLATION AFTER A LONG PERIOD OF STORAGE Severe damage to the drive can result if it is operated after a long period of storage or inactivity

Página 19 - 6.0 THEORY

8.0 INPUT AC REQUIREMENTS Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain

Página 20 - % SPEED

9.0 VOLTAGE SELECTION9.1 INPUT VOLTAGE RATINGS 115/230 Volt MICRO Seriesdrivesareratedfor240/120Vac,50-60Hzinput.Thedrivewillfunction

Página 21

11.0 MICRO SERIES POWER WIRING DIAGRAM Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result.

Página 22

12.0 INITIAL POWER UP Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain cha

Página 23

TABLE OF CONTENTS1.0 GENERAL ... 4 PRODUCT CHANGES ...

Página 24 - 7.0 INSTALLATION

 3. If the motor is rotating in the wrong direction, press the “STOP” key, remove power from the drive, wait three minutes for the

Página 25

13.2 MICRO SERIES DISPLAY The following describes the possible display configurations for the SPEEDMASTER MICRO Series drive.13.2.1 MICRO SERIES DI

Página 26 - 8.0 INPUT AC REQUIREMENTS

30 The following table shows the possible DRIVE STATUS indications that can appear on the drive display:DRIVE STATUS TABLE DISPLAY DESCRIPTION ST

Página 27 - 10.0 POWER WIRING

13.2.2 MICRO SERIES DISPLAY IN RUN MODE WhenthedriveisintheRUNmode,thedefaultdisplaywilllooklikethis: AsintheSTOPmode,theENTER

Página 28

3213.2.3 MICRO SERIES DISPLAY IN FAULT MODE When the drive trips on a fault, the display will automatically change to the FAULT display, which indic

Página 29 - 12.0 INITIAL POWER UP

33 Thetable belowshowsthe possibleSPEEDREFERENCESOURCEindications fortheauxiliarystatus display:SPEED REFERENCE TABLE DISPLAY DESCRI

Página 30 - 13.0 KEYPAD CONTROL

14.0 CONTROL WIRING14.1 GENERAL14.1.1 KEYPAD CONTROL Thedrivecanbecontrolledbythekeypadorbycontroldeviceswiredtotheterminalstrip.T

Página 31

14.2 START/STOP AND SPEED CONTROL14.2.1 REMOTE MODE SELECTION The REMOTE mode can be selected by one of two methods: 1. Program Parameter 30 - CO

Página 32

14.2.3 ALTERNATE TWO-WIRE START/STOP CONTROL METHOD  This method requires TB-13C to be set for RUN REVERSE, which will disable TB-1 a

Página 33

14.2.4 THREE-WIRE START/STOP CONTROL A three-wire start/stop circuit can be accomplished by one of two methods on the MICRO Series drive. Follow the

Página 34

TABLE OF CONTENTS (cont’d.)19.0 MICRO SERIES PID SET POINT CONTROL ... 77 FEEDBACK DEVICES . . . . . . . . . . . . . . . .

Página 35

14.2.5 SPEED REFERENCE SIGNALS Thedriveallowsforthreeanalogspeedreferenceinputs:aspeedpotentiometer(10,000Ohm),0-10VDC,or 4-20 mA.

Página 36 - 14.0 CONTROL WIRING

 JOG TheJOGfunctiononlyworkswhenthedriveisinREMOTEmode,andonlywhenthedriveisinaSTOPcondition.TB-13Bcanbeprogrammedforeith

Página 37

15.0 MICRO SERIES CONTROL WIRING DIAGRAMS15.1 MICRO SERIES TERMINAL STRIP Shown below is the terminal strip on the main control board, along with a

Página 38

15.2 TWO-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintained contact(s

Página 39

15.3 THREE-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentary contacts(

Página 40

15.4 SPEED POT AND PRESET SPEED CONTROL ShownbelowisthewiringdiagramforacontrolschemethatutilizesaspeedpotandPRESETSPEEDSforspeed

Página 41

16.0 PROGRAMMING THE MICRO SERIES DRIVE16.1 PROGRAMMING THE PARAMETERS The MICRO Series keypad serves two purposes: operating the drive w

Página 42

Once the correct password is entered, the PROGRAM mode will be entered and the first parameter will be displayed, which is Parameter 0 - LINE VOLTS.

Página 43

16.2 PARAMETER ACCESS USING SPEED DIAL SPEED DIAL is used to access parameters quickly using the parameter number. Once accessed, the

Página 44

4717.0 PARAMETER MENUNOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE

Página 45

3IMPORTANT NOTICEThe following , and information is supplied to you for your protection and to provi

Página 46 - 20.00 HZ

48NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE3:IFLINEVOLTSIS

Página 47

49PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT  43 @TB10A 0.00-360.0HZ(NOTE2) 60.00Hz 44 TB10B O

Página 48

50PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT 65 PROGRAM MAINTAIN, RESET 60,   RESET50(NOTE4) RES

Página 49 - 17.0 PARAMETER MENU

5118.0 DESCRIPTION OF PARAMETERS 0 LINE VOLTS (LINEVOLTAGE) This parameter calibrates the drive for the correct input voltage, and can be set

Página 50

1-4 SPEED #1-#4 (PRESETSPEEDS#1,#2,#3,AND#4) PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact clo

Página 51

Example:Thecriticalfrequencyis21Hz,andabandwidthof2Hzisdesired.Therefore,setSKIP#1to20HzandsetSKIPBANDWIDTHto2Hz.Thisr

Página 52

54 NOTE 1: 240/120 Vac units have the same limits as 240/200 Vac units. NOTE 2: The parameter value can be set below the minimum value shown, but th

Página 53

11 MAX FRQ (MAXIMUMFREQUENCY) Thisparameterdefinestheupperlimitofthedrive’sspeedrange.MAXFRQisusedinconjunctionwithMINFRQ(Par

Página 54

14 DYN BRAK (DYNAMICBRAKE) This parameter enables the dynamic braking circuit. Set this parameter to ON only if the optional dyna

Página 55

 The“speed-compensated”thermaloverloadcircuitoffersadditionalprotectionfromhighloadconditionsatlowspeeds,wheremotorcoolingisoften

Página 56

1.0 GENERAL1.1 This manual covers the LEESON MICRO Series Inverters.1.2 PRODUCT CHANGES LEESON Electric reserves the right to discontinue or

Página 57

18 BASE (BASEFREQUENCY) The BASE FREQUENCY determine the V/Hz ratio by setting the frequency at which the drive will output full

Página 58

20 AC BOOST (ACBOOST) AC BOOST is similar to FX BOOST, but is only active when the drive is accelerating. During acceleration, theoutputvoltage

Página 59 - OUTPUT CURRENT (%)

22 TORQUE (TORQUECURVESELECTION) ThisparameterisusedtoselectwhethertheoutputofthedrivefollowsaconstantorvariableV/Hzcurve.The

Página 60

25 START (STARTMODE)  Automaticstartofequipmentmayresultindamagetoequipmentand/orinjurytopersonnel!Automaticstartshouldonlybe

Página 61 - OUTPUT VOLTAGE (%)

27 ROTATION (ROTATIONDIRECTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein

Página 62

29 MANUAL (MANUAL) This parameter selects the speed reference source when the drive is set for MANUAL speed control (seeparameter28 - AUTO/MAN

Página 63

33 SPEED DP (SPEEDDECIMALPOINT) This parameter is used to move the decimal point location in the speed display. This parameter will not have any

Página 64

Example:SLEEP THRESHOLD isset to15Hz andSLEEP DELAYisset to60seconds. Ifthe drive operates below 15Hzfor60 seconds, the dr

Página 65

41 AIN FLTR (ANALOGINPUTFILTER) Thisparameteradjuststhefilterontheanaloginputterminals(TB-5AandTB-5B)toreducetheeffectofanyel

Página 66

47 TB13A (TB-13AINPUTFUNCTION) This parameter is used to select the function of terminal TB-13A. Closing TB-13A to TB-2 activates the TB-13

Página 67

2.0 MICRO SERIES SPECIFICATIONS Storage Temperature -20° to 70° C Ambient Operating Temperature Chassis -10° to 55° C  (With2.5and8kHZcar

Página 68

49 TB13C  (TB-13CINPUTFUNCTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein

Página 69

50 TB13D  (TB-13DFUNCTION)  STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaults!The

Página 70

SPEED #3 value. See Parameter 3 - SPEED #3 in Section 18.0 - DESCRIPTION OF PARAMETERS, ILIMIT  CURRENTLIMIT-Therelayenergizeswhenthedrive

Página 71

71 SPD=0HZ Therelayenergizeswhenthereisnooutputtothemotor,foranyreason,suchas:drive    isinSTOPmode,driveisinRUNmode

Página 72

NOTE 2: If a RESET command (Parameter 65 - PROGRAM) is issued through the serial link, this parameter will not default back to

Página 73

65 PROGRAM (PROGRAMFACTORYDEFAULTS) STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaul

Página 74

70 PID MODE (PIDMODESELECT) This parameter activates the PID function, and selects whether the PID control will be direct or reverse acting.

Página 75

NOTE:Ifareverseactingfeedbackdeviceisbeingused,FB@MINshouldbesettothemaximumprocessvariable value, and FB @ MAX should be set to

Página 76

relayoropen-collectoroutputwillde-energize,whichopensthestartcontactandstopsthedrive.WhenthesignalisequaltoorgreaterthantheMI

Página 77

19.0 MICRO SERIES PID SET POINT CONTROL PID Set point Control allows the MICRO Series Control to maintain a process set point, such as PSI orCFM,w

Página 78

64.0 MICRO SERIES DIMENSIONS4.1 TYPE 1 ENCLOSEDWRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ≤ 7

Página 79

 Forareverseactingtransducer,setParameter75-FB@MINtothemaximumprocessvariablefeedbackvalue,andsetParameter76-FB@MAXtothe

Página 80

eachtype,sothesametypeofsignalcannotbeusedfortransducerfeedbackandsetpointreference.For example,a4-20mAsignalfromatransducer

Página 81

When the drive is in PID mode, the DRIVE STATUS portion of the display will indicate actual output frequency(inHertz)insteadofRUN,andtherig

Página 82

8120.0 TROUBLESHOOTING The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please con

Página 83 - 20.0 TROUBLESHOOTING

82FAULT MESSAGES FAULT DESCRIPTION POSSIBLE CAUSES EXTERNAL Externalfault:TB-13Disopenorclosed ChecksettingofParameter to TB-2, depe

Página 84

8321.0 USER SETTING RECORDPARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 0 LINE VOLTS AUTO 1

Página 85 - 21.0 USER SETTING RECORD

84PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 20 AC BOOST .0% 21 SLIP CMP .0% 22 TORQUE

Página 86

8585PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 42 TB10A OUT NONE 43 @TB10A 60.00Hz 44

Página 87

86PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 74 PID FB TB-5A 75 FB @ MIN 0.00% 76 FB

Página 88

EC DECLARATION OF CONFORMITYWe,LEESON Electric1051 Cheyenne AvenueGrafton, Wisconsin 53024 U.S.A.declareundersoleresponsibilitythatthefollowing

Página 89 - LEESON Electric

7WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q

Página 92 - A Regal Brand

A Regal BrandLEESON ElectricGrafton, Wisconsin 53024 U.S.A.PH: 262-377-8810FAX: 262-377-9025www.leeson.comREGAL BELOIT CANADAMississauga (Toronto), On